我是标题
Single cold model | GF-4 | GF-5 | GF-6 | GF-8 | GF-12 | GF-24 | ||
Heating and cooling models | GF-4R | GF-5R | GF-6R | GF-8R | GF-12R | |||
Air supply method | Front air supply | |||||||
Cooling capacity | W | 4000 | 5000 | 6000 | 8000 | 12000 | 24000 | |
Heating capacity | W | 4000 | 4000 | 5000 | 6300 | 6400 | ||
temperature range | 20-35+2 | |||||||
Circulating air volume | m3/h | 1200 | 1200 | 1400 | 2000 | 2000 | 4100 | |
Rated current | A | 10 | 10.5 | 11 | 14.5 | 24.5 | 40 | |
Input power | AC-380V/50Hz | |||||||
Refrigerant | R142b | |||||||
Power consumption | Refrigeration | W | 3100 | 3150 | 3220 | 4880 | 9150 | 14000 |
Heating | W | 4200 | 4200 | 5200 | 6600 | 6800 | ||
Total Weight | Indoor unit | Kg | 70 | 75 | 80 | 100 | 150 | 250 |
The outdoor unit | Kg | 130 | 150 | 180 | 200 | 240 | 580 | |
Dimensions (length * width * height) | Indoor unit | mm | 520*330*1210 | 520*330*1210 | 620*330*1210 | 720*380*1410 | 770*425*1660 | 910*620*1660 |
The outdoor unit | mm | 910*490*710 | 910*490*710 | 1160*560*890 | 1310*610*960 | 1510*660*1216 | 1270*855*1240 | |
annex | Liquid tube (diameter * length) | mm | ₵12*5000 | ₵12*5000 | ₵10*5000 | ₵16*5000 | ₵12*5000 | ₵16*5000 |
Trachea (diameter * length) | mm | ₵16*5000 | ₵16*5000 | ₵19*5000 | ||||
Unit connection line | mm | 7000 |
Single cold model | G-4 | G-6 | ||
Heating and cooling models | G-4R | G-6R | ||
Air supply method | Front air supply | |||
Cooling capacity | W | 4000 | 6000 | |
Heating capacity | W | 4000 | 5000 | |
temperature range | 20-35+2 | |||
Circulating air volume | m3/h | 1200 | 1400 | |
Rated current | A | 10 | 11 | |
Input power | AC-380V/50Hz | |||
Refrigerant | R134a | |||
Power consumption | Refrigeration | W | 3720 | 3220 |
Heating | W | 4200 | 5200 | |
Total Weight | Indoor unit | Kg | 60 | 80 |
The outdoor unit | Kg | 130 | 180 | |
Dimensions (length * width * height) | Indoor unit | mm | 900*290*580 | 900*290*580 |
The outdoor unit | mm | 900*480*700 | 900*480*700 | |
annex | Liquid tube (diameter * length) | mm | ₵12*5000 | ₵12*5000 |
Trachea (diameter * length) | mm | ₵16*5000 | ₵19*5000 | |
Unit connection line | mm | 7000 |
High-temperature special air conditioners are used in steel plants, metallurgical industries, driving cabs, electrical rooms, high-voltage rooms, and four coking cars (pulling coke, quenching car, coal loading car, pushing coke car), etc. It can keep the room between 22-35 ℃. This series of air conditioners are divided into split type and integral type. The installation is flexible and convenient. Split high-temperature air conditioner can be divided into: Hanger G and Cabinet GF series according to the installation method of the internal unit
Characteristics of high temperature special air conditioner
Using imported flexible scroll compressors (world famous brands such as Copeland), high energy efficiency and high reliability.
The condenser and evaporator use thick-walled high-efficiency internally-threaded heat exchange tubes with a fin spacing of> 2.9mm; you can choose to perform electrophoretic anti-corrosion treatment on the two devices, which can make the equipment work safely and reliably at high temperatures such as coking plants for a long time. Dust and high vibration environment.
The electrical box adopts high-level dust-proof treatment to prevent dust from damaging electrical components.
Using filters from world famous brands such as Emerson to ensure safe and more efficient operation of the refrigeration system,
Optimized system matching, the use of high-temperature refrigerant R142b, greatly improves the humidity of the air-conditioning environment, and the limit temperature can reach 75 ° C.
The refrigeration system uses an expansion valve as a throttling element and is equipped with a liquid reservoir, which can adjust the liquid supply of the refrigeration system according to environmental changes to achieve the best use of the equipment.
Condensing fan adopts IP54 protection level, F-class insulation inner rotor metal blade air blade
Reasonable structural design, solid sheet metal frame, and special shock-absorbing design of components make the overall seismic resistance of the equipment strong, suitable for use in steel plants and coking plants.